ICA UPS M300FA33 Capacity 300 KVA, inverter only works when the AC input voltage is low or loss. When the AC input voltage is in normal condition, ICA UPS will stabilize and filter the AC input voltage and supply a clean and stable AC voltage to the ICA UPS output and charge the battery. When the AC input voltage is low or loss, inverter will replace it and supply a stable AC voltage within a very short transfer time.
|
Description |
: |
UPS M300FA33 |
Capacity |
: |
300 KVA / 270 KW |
Nominal Voltage |
: |
380/400/415 Vac (3 Ph + N + PE) |
Voltage Range |
: |
208 - 478 Vac |
Frequency Range |
: |
40 - 70 Hz |
THD |
: |
3 % (100% non-Linear load) |
Output Voltage |
: |
380/400/415 Vac (3 Ph + N + PE) |
Voltage Regulator |
: |
± 1% |
Efficiency |
: |
95 % |
Battery Voltage |
: |
± 192 ± 204 ± 216 ± 228 240Vdc, battery quantity (optional) |
Charger Current |
: |
100 A (Max) |
Backup time |
: |
Depends on the capacity of external batteries |
Transfer Time |
: |
Utility to Battery 0 ms, Utility to Bypass 0 ms |
Overload Batt Mode |
: |
Load ≤110% last 10 min, ≤125% last 1 min, ≤150% last 1 s, ≥150% shut down UPS immediately |
Bypass Mode |
: |
Breaker (25 KVa : 40 A / 30 KVa : 60 A) |
Short circuit |
: |
Hold whole system |
Operating Temp |
: |
0 - 40 °C |
Storage Temp |
: |
-25 ~ 55 °C |
Noise level |
: |
<70 dB |
Dimension(DxWxH) |
: |
1100 x 600 x 2000 mm |
Weight |
: |
307 Kg |
|
ACCESSORIES |
|
|
|
|
|
N/A |
N/A |
N/A |
N/A |
N/A |
|