ICA UPS SE2100 Capacity 2000VA. Because the UPS is the true on-line system, conditioned power is provided continuously to the attached load. The UPS constantly regulates and filter the AC input voltage and supply a clean and stable AC voltage to the output and charge the batteries. When the AC input voltage low or loss, the UPS protects the load instantaneously and supply a stable AC voltage without any transfer time.
|
Description |
: |
UPS SE2100 |
Capacity |
: |
2000 VA / 1800 W |
AC Voltage |
: |
110 ~ 290 V |
|
: |
1 Phase |
AC Frequency |
: |
45 ~ 65 Hz |
AC Protection |
: |
12 A |
DC Voltage |
: |
72 V |
DC INT Battery |
: |
6 x 12 V, 7 Ah |
DC Protection |
: |
FUSE |
CHG Topology |
: |
SWITCHING REGULATION |
CHG Floating Voltage |
: |
81.6 V |
INV Wave Form |
: |
SINEWAVE |
INV Distorsion |
: |
< 3% THD |
INV Topology |
: |
Online Double Conversion |
INV Voltage |
: |
220 ± 1% V |
INV Frequency |
: |
50 ± 1% Hz |
INV Efficiency |
: |
≥ 90% |
Transfer Time When AC In Loss |
: |
0 ms |
Transfer Time STS |
: |
2 ms Inverter to Bypass, 0 ms Back To Inverter |
Back Up Time |
: |
10 min |
BZR AC Input Abnormall |
: |
INTERMITTENT SOUND WITH 4 SECONDS INTERVAL |
BZR Battery Low |
: |
INTERMITTENT SOUND WITH 1 SECONDS INTERVAL |
Opera Temp |
: |
0 – 40 °C |
Dimension(DxWxH) |
: |
470 x 191 x 336 mm |
Weight |
: |
25.8 Kg |
|
ACCESSORIES |
|
|
|
|
|
N/A |
N/A |
N/A |
N/A |